VMLK SERIES
Round air flow meter for recording or monitoring air flow
Continuous air flow measurement
Recording of measured values and their transfer to slave controllers
For combination with LABCONTROL control components
Regulation of air flow for fume hoods by transmitting a signal to frequency converters
Measurement accuracy ± 5%, even when installed in unfavorable air flow conditions
Housing made of flame retardant polypropylene (PPs)
Housing tightness according to EN 15727 class C
Optional equipment
With flanges on both sides
Application
Round air flow meter LABCONTROL VMLK series for automatic monitoring of air flow levels coming from fume cupboards and fume hoods
Suitable for polluted air
Regulation of air flow for fume hoods by transmitting a signal to frequency converters
Simplified commissioning, testing and maintenance
Can be installed as a permanent network element due to low resistance
Characteristics
High measurement accuracy under all air flow conditions
Effective pressure range: approx. 5 – 250 Pa
Options
VMLK: Air flow meter
VMLK-FL: Air flow meter with flanges on both sides
Details and characteristics
Assembled device with mechanical components and automation, completely ready for commissioning
Average differential pressure sensor for air flow measurement; Can be detached for cleaning
Assembled control unit with measuring tubes