PURELINE18 SERIES
Slot diffusers with slot size 18 mm (nominal width) and adjustable guide rollers
- Nominal length 600 – 2000 mm (guide length 100 mm), 1 or 2 slots
- Air flow level 5 – 84 l/s or 17 – 302 m³/h
- Individually adjustable guide elements for horizontal, angled or vertical air supply
- Air supply in one direction or multi-directional depending on the requirements of the room
- Uniform air flow reduces ceiling contamination resulting from air leaks from the room
- The guide elements have grooves for more precise positioning
Additional equipment and accessories
- Attractive appearance thanks to aluminum profile with anodized or powder-coated finish
- Symmetrical or asymmetrical plenum position
- Soundproofed plenum chamber
- End plates, end angles, corner sections
- Different looks thanks to the choice of black, gray or white guide elements
Description
Slot diffusers direct air from the air conditioning system into the room horizontally, at an angle or vertically.
The air flow obtained at the outlet of the diffuser allows one to achieve high ejection values, thereby quickly reducing the flow rate and leveling out the temperature difference between the supply air and the air in the room.
As a result, there is a mixing of air flows in comfort zones, with a good distribution of air jets throughout the room and a small turbulent vortex in the area where people are present.
PureLine18 series slot diffusers are factory equipped with manually adjustable guide elements.
The direction of air flow can be changed if necessary.
Air supply is carried out horizontally in one direction or in different directions.
Other schemes: heating mode with vertical air supply; angular air supply.
The temperature difference between the supply air and the room can range from –10 to +10 K.
Flap blade (optional) to balance air flow simplifies operation.
To create an attractive, unified room design, the PureLine18 series diffusers can also be used for exhaust ventilation.
Nominal length 600 – 2000 mm, in 100 mm increments
Number of slots 1 or 2
Min. air flow, where ΔtZ = -10 K 5 l/s or 17 m³/h
Max. air flow level, at LWA ≅ 50 dB(A) 84 l/s or 302 m³/h
Temperature difference between supply air and room –10 to +10K
① Front panel, 1 or 2 slots
②Adjustable guide drums
③ Screw fastening
⑥ Neck
⑦ Static chamber
⑧ Hanging bracket
⑨ Connection
Optional
④ End plate
⑤ End bracket
⑩ Seal
⑪ Valve blade for balancing air flow